9F59UBC202
Serie: 8.3kV ETP Fuses
ETP 8300V : 25K / 15T Aufbau: 202
The Sure Guard ETP back-up current-limiting fuses are designed to protect overhead distribution systems and are used in series with another protective device (such as an expulsion fuse). This combination limits the high-fault current to a safe level, thus providing protection through the complete range. As its name implies, the “ETP” is for External Transformer Protection. For conventional transformers protected by expulsion-fuses cutouts, the ETP can be installed in series with the cutout. For self protected transformers, the ETP can be applied on the high-voltage bushing in series with the internal transformer expulsion fuse.
ETP 8300V : 25K / 15T Aufbau: 202
The Sure Guard ETP back-up current-limiting fuses are designed to protect overhead distribution systems and are used in series with another protective device (such as an expulsion fuse). This combination limits the high-fault current to a safe level, thus providing protection through the complete range. As its name implies, the “ETP” is for External Transformer Protection. For conventional transformers protected by expulsion-fuses cutouts, the ETP can be installed in series with the cutout. For self protected transformers, the ETP can be applied on the high-voltage bushing in series with the internal transformer expulsion fuse.
Datasheets
pdf - 811.57 KB
Teilenummer | 9F59UBC202 |
Beschreibung | ETP 8300V : 25K / 15T Aufbau: 202 |
EAN / UPC-Code | 782001399016 |
Bemessungsbetriebsspannung AC UL | 8300 V |
Wechselstrom oder Gleichstrom | AC |
AC max. Strombelastbarkeit/Ausschaltvermögen: I1 | 50 kA |
Designdetails | 202 |
Material der Kontakte | Messing |
Produktdurchmesser | 55.6 mm |
Produktlänge | 349.5 mm |
Verpackungsmenge | 1 EA |
Verpackungsgewicht | 1.8012 kg |
Verpackungsbreite | 60.5 mm |
Verpackungslänge | 60.5 mm |
Verpackungshöhe | 435.1 mm |
Produktgruppe | IEEE-Mittelspannungssicherungen |
Material des (Sicherungs-) Körpers | Epoxy |
Produktgewicht | 1.7155 kg |